70
Control
7. Restore and fasten the upper mounting board in its original position, and close the AHU Kit
enclosure again (see “4.1 Installation of AHU Kit“ – step 5).
Case 3: 0–10 V demand control by an external BMS
To set the thermostat for 0–10 V demand control by an external building management system
(BMS), perfom the following steps:
1. Open the AHU Kit enclosure (see “4.1 Installation of AHU Kit“ – step 2), and remove the up-
per mounting board.
2. On the CZ-CAPBC2 PCB, located on the lower mounting board inside the AHU Kit en-
closure, remove the existing wiring from the thermostat TR-16 at the analogue input (AI)
contacts No. 3 and 4, and replace it with the 0–10 V signal wiring from the external BMS
(see diagram below). Make sure that correct polarity is observed: terminal 3 = negative (–),
terminal 4 = positive (+).
1
3
AC IN
(BLK)
1
2
OC
(BLU)
1
3
RC
(BLU)
1
2
EXCT
(RED)
1
2
3WAY
(BLK)
3
4
5 1
3
OP1
(YEL)
1
3
FAN
(WHT)
5
7
91
3
T20
(GRY)
1
3
TRANS-P
(WHT)
1
2
TRANS-S
(WHT)
3
4
BRN
BRN
WHT
WHT
RED
RED
TR1
1
2
PMV
(WHT)
3
4
5 6 1
2
HBS
(YEL)
CR-UXRP71B-P
1
2
TA
(YEL)
BLK
BLK
1
2
E1
(RED)
BLK
BLK
1
3
E3
(BRN)
BLK
BLK
1
2
BL
(GRN)
BLK
BLK
1
3
FS
(RED)
RED
1
2
PNL
(BRN)
GRN
1
2
FAN DRIVE
(WHT)
WHT
RED
BLK
BLU
PNK
BLU
WHT
BLK
RED
WHT
L N
U1 U2 R1 R2
EX1 EX2
YEL
BLU
BLK
WHT
RED
1
2
3
4
5 1
3
3WAY (WHT)
POWER (WHT)
CR-SV80B
1
3
SV1 (RED)
5
7
9
BLK
WHT
RED
YEL
BLU
6
1
2
3
4
5 6
CONNECTOR 6P
(YEL)
1
3
SV2 (RED)
5
7
9
BLK
WHT
RED
YEL
BLU
1
2
3
4
5 6
CONNECTOR 6P
(YEL)
RED
WHT
BLK
1Z
7 5
8 3 1
2Z
7 5
8 3 1
1
3
OP3
(YEL)
TERMINAL
VLT
GRY
1Z5 1Z3
TERMINAL
OP3 2Z7 05 06
YEL
ORG
VLT
WHT
BRN
M1.1 M1.2 M1.3 M1.4 M1.5
TERMINAL
TA1 TA2 E1.1 E1.2 E3.1 E3.2 BL1 BL2 FS1 FS2
TERMINAL
FD1 FD2
1
2
FILTER
(WHT)
RED
WHT
FI1 FI2
1
3
HU1
(RED)
VLT
BRN
HU1 HU2
CZ-CAPBC2
COM DO2 COM DO1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
CN2
CN1
4POL
PK1-B
10
PK1-A
PAW-T10
T10
98
1
2
3
4
5
6
1
2
3
4
7 6 5
(WHT)
1
2
3
4
5
6
T10
(YEL)
+
E
1
2
OPTION
(WHT)
3
4
5
6
YEL
RED
WHT
BLK
BLU
ORG
ON1 ON2 ON3 ON4 ON5 ON6
TR-16
PT100
COM DI1 DI2 DI3 COM DO2 COM DO1
TERMINAL
12345
678910
PT10 PT9 PT8
TERMINAL
BLK
BLU
BRN
YEL
RED
WHT
RED
RED
WHT
+-
RED
BLK
BLK
ORG
RED
YEL
BLK
GRY
WHT
BLU
YEL
ORG
BRN
BRN
ORG
YEL
BLU
WHT
BLK
CZ-RTC2
R1 R2
WHT
BLK
ORG
ORG
GRY
RED
WHT
RED
WHT
WHT
BLK
PNK
BLU
BLK
YEL
BLU
RED
t°
TH1
t°
TH2
t°
TH4
t°
TH5
ORG
RED
YEL
BLK
GRY
ORG
RED
YEL
BLK
GRY
WHT
GRY
WHT
M1.6 M2.1 M2.2 M2.3 M2.4 M2.5
ORG
RED
YEL
BLK
WHT
WHT
BLK
Connect 0–10 V signal wiring from
BMS here (observing correct polarity!)
Disconnect the
wiring of the
TR-16 controller
– +
Comentarios a estos manuales