Installation
4.4.3 Installation of thermistor on heat exchanger pipe middle
Installation of thermistor on heat exchanger pipe middle – PACi systems
Mount “E2” thermistor to heat exchanger pipe middle according to the following instructions.
1. Attach the heat exchanger pipe middle thermistor in the middle of each pass-line (pipe) in
the heat exchanger.
2. Cover the thermistor and pipe with aluminum tape (eld-supplied).
3. Fix thermistor with two bands. Then, run the wire downwards in a loop, to avoid putting ten-
sion to it
4. Cover the aluminum tape with thermal insulation. And also cover the sensor (copper portion)
with thermal insulation completely.