Product description
3.8 Technical data and limitations
Important
Apart from the technical data and limitations given in the following tables, the technical data and
limitations of the relevant outdoor units, local wiring and piping design regulations and approved
best practices need to be observed in installation procedures.
Technical data and limitations – ECOi and ECO G systems
HP 5 10 20
Model PAW-160MAH2(L) PAW-280MAH2(L) PAW-560MAH2(L)
Nominal cooling capacity kW 14.0 28.0 56.0
Nominal heating capacity kW 16.0 31.5 63.0
Air volume (Cooling) Min m³/h 1,140 3,500 7,000
Max m³/h 2,600 5,000 10,000
AHU DX coil heat exchanger
volume
Min dm
3
1.7 2.8 5.6
Max dm
3
2.8 5.4 10.7
Bypass factor 0.9 (recommended) 0.9 (recommended) 0.9 (recommended)
Power source V / ph / Hz 230 / 1 / 50 230 / 1 / 50 230 / 1 / 50
Dimensions (enclosure) H x W x D mm 278 x 278 x 180 278 x 278 x 180 278 x 278 x 180
Net weight Advanced / Light kg 4.25 / 3.98 4.80 / 4.53 4.25 / 3,98
Protection class IP65 IP65 IP65
Piping length Min / Max m 10 / 100 10 / 100 10 / 100
Max. branch pipe length m 12 12 12
Max.branchpipelengthdifferenceafterrstbranch m 10 10 10
Elevation difference (in/out) Max m 10 10 10
Piping connections Liquid pipe Inch (mm) 3/8 (9.52) 3/8 (9.52) 5/8 (15.88)
Gas pipe Inch (mm) 5/8 (15.88) 7/8 (22.22) 1 1/8 (28.58)
Intake temperature of
AHU Kit
Cooling (Min / Max) °C 18 / 32 °C DB
(13 / 23 °C WB)
18 / 32 °C DB
(13 / 23 °C WB)
18 / 32 °C DB
(13 / 23 °C WB)
Heating (Min / Max) °C 16 / 30 °C DB 16 / 30 °C DB 16 / 30 °C DB
Ambient temperature
(outdoor unit)
Cooling (Min / Max) °C -10 / 43 °C DB -10 / 43 °C DB -10 / 43 °C DB
Heating (Min / Max) °C -20 / 15 °C WB -20 / 15 °C WB -20 / 15 °C WB
HP 30¹ 40¹ 50¹ 60¹
Model PAW-280MAH2(L) +
PAW-560MAH2(L)
PAW-560MAH2(L) +
PAW-560MAH2(L)
PAW-560MAH2(L) +
PAW-560MAH2(L) +
PAW-280MAH2(L)
PAW-560MAH2(L) +
PAW-560MAH2(L) +
PAW-560MAH2(L)
Nominal cooling capacity kW 84.0 112.0 140.0 168.0
Nominal heating capacity kW 95.0 127.0 155.0 189.0
Air volume (Cooling) Min m³/h 15,000 20,000 25,000 30,000
Max m³/h 10,500 14,000 17,500 21,000
AHU DX coil heat exchanger
volume
Min dm
3
8.4 11.2 14.0 32.1
Max dm
3
16.1 21.4 26.8 16.8
Bypass factor 0.9 (recommended) 0.9 (recommended) 0.9 (recommended) 0.9 (recommended)
Power source V / ph / Hz 230 / 1 / 50 230 / 1 / 50 230 / 1 / 50 230 / 1 / 50
Dimensions (enclosure) H x W x D mm for dimensions of single enclosure: see upper table
Net weight kg for net weight of single enclosure: see upper table
Protection class IP65 IP65 IP65 IP65
Piping length Min / Max m 10 / 100 10 / 100 10 / 100 10 / 100
Max. branch pipe length m 12 12 12 12
Maxi.branchpipelengthdifferenceafterrstbranch m 10 10 10 10
Elevation difference (in/out) Max m 10 10 10 10
Piping connections Liquid pipe Inch (mm) 3/4 (19.05) 3/4 (19.05) 3/4 (19.05) 3/4 (19.05)
Gas pipe Inch (mm) 1 1/4 (31.75) 1 1/2 (38.15) 1 1/2 (38.15) 1 1/2 (38.15)
Intake temperature of
AHU Kit
Cooling (Min / Max) °C 18 / 32 °C DB
(13 / 23 °C WB)
18 / 32 °C DB
(13 / 23 °C WB)
18 / 32 °C DB
(13 / 23 °C WB)
18 / 32 °C DB
(13 / 23 °C WB)
Heating (Min / Max) °C 16 / 30 °C DB 16 / 30 °C DB 16 / 30 °C DB 16 / 30 °C DB
Ambient temperature
(outdoor unit)
Cooling (Min / Max) °C -10 / 43 °C DB -10 / 43 °C DB -10 / 43 °C DB -10 / 43 °C DB
Heating (Min / Max) °C -20 / 15 °C WB -20 / 15 °C WB -20 / 15 °C WB -20 / 15 °C WB
1 Not applicable for ECO G systems.