Product description
The light version, denominated by the letter “L” in the model name, contains the following
components:
IP65 case
Control unit including transformer
Relays
Terminal boards
Remote controller (CZ-RTC2)
PCBs for the expansion and RAP valves
PCB for T10 connection (PAW-T10)
Expansion valve (only for ECOi and ECO G)
Refrigerant temperature sensors (E1, E2/E3)
Air intake and air outlet temperature sensors (TA, BL)
In addition to this, the advanced version, without the letter “L” in the model name, contains also
the following components:
Thermostat including an additional temperature sensor to be used either for
room supply air or ambient air temperature
Interface for 0–10 V control (CZ-CAPBC2)
The heat exchanger, fan and fan motor must be eld supplied.
Control functions provided as standard by integral components
CZ-RTC2 Timer remote controller
Operation-ON/OFF
Mode selection
Temperature setting
Parameter settings
Additional Thermostat (advanced version only)
Target temperature setting based on ambient temperature with proportional
integral logic*
Demand control based on room supply air temperature to enhance comfort and
efciency*
* Only one of these two options can be chosen at a time.