Panasonic PAW280MAH2 Instrucciones de operaciones Pagina 45

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 74
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 44
45
Installation
4.4.2 Installationofthermistoronliquidpipe
Mount “E1” thermistor to liquid pipe of AHU heat exchanger according to the following
instructions.
1. Attach the liquid pipe thermistor to the liquid pipe located in the lowest position after the
distributor in the heat exchanger.
2. Cover the thermistor and pipe with aluminum tape.
3. Cover the aluminum tape with thermal insulation.
4. Fix thermal insulation and wiring with two bands. Then, run the wire downwards in a loop, to
avoid putting tension to it.
Vista de pagina 44
1 2 ... 40 41 42 43 44 45 46 47 48 49 50 ... 73 74

Comentarios a estos manuales

Sin comentarios