Electrical Wiring
Section D Section E Section F
No. Name Description Note No. Name Description Note No. Name Description Note
1 L Power supply 230 V AC /
max. 1 A
1 U1 (OC) IU/OU
communication
5 V AC 1 E1-1 E1 sensor 5 V DC
2 N Neutral conductor 230 V AC /
max. 1 A
2 U2 (OC) IU/OU
communication
5 V AC 2 E1-2 E1 sensor 5 V DC
3 PE Protective earthing 3 R1 Needed for group
wiring
1
16 V DC 3 E2-1 /
E3-1
E2 sensor (PACi) /
E3 sensor
3
5 V DC
4 1Z-5 Relay 1Z, Pin 5,
Blower out
max. 230 V AC
/ 5 A
4 R2 Needed for group
wiring
1
16 V DC 4 E2-2 /
E3-2
E2 sensor (PACi) /
E3 sensor
3
5 V DC
5 1Z-3 Relay 1Z, Pin 3,
Blower out
max. 230 V AC
/ 5 A
5 M1-1 For expansion valve
1
12 V DC 5 M2-1 Spare, not used
6 OP3 CR8-SV80B, OP3,
Pin 1,
Blower protection
230 V AC 6 M1-2 For expansion valve
1
12 V DC 6 M2-2
7 2Z-7 Relay 2Z, Pin 7,
Blower protection
230 V AC 7 M1-3 For expansion valve
1
12 V DC 7 M2-3
8 HU1 Humidier max. 230 V AC
/ 3 A
8 M1-4 For expansion valve
1
12 V DC 8 M2-4
9 HU2 Humidier max. 230 V AC
/ 3 A
9 M1-5 For expansion valve
1
12 V DC 9 M2-5
10 Blind 10 M1-6
2
12 V DC 10 Blind
1 For ECOi and ECO G systems only.
2 For PAW-160MAH2(L) and 280MAH2(L) only. In this case, there are 6 instead of 5 pins.
3 E2 sensor in case of PACi, E3 sensor in case of ECOi and ECO G.
5.5 Connection of wiring to terminals
Connect wiring to the terminals according to the following instructions.
Stranded wire
1. Cut the wire end with cutting pliers, then strip the insulation to expose the stranded wiring
about 10 mm and tightly twist the wire ends.
Strip 10 mm
Wire-end
sleeve
2. Using a at-blade screwdriver, loosen the terminal screw(s) on the terminal plate.
3. Attach a wire-end sleeve to each stripped wire end using a crimping tool.