Ventilation theory and air handling units
2 Ventilation theory and air handling units
2.1 Purpose of air-conditioning
The purpose of air-conditioning is to provide comfortable indoor air conditions for the room oc-
cupants and to provide energy saving potentials for the owner.
Comfort
If room occupants feel “comfortable“ in a given room, depends mainly on the following two
factors:
air temperature
relative air humidity
However, optimum working or living conditions do not only exist at a specic setpoint of room
temperature and room humidity, but also within a certain band width of the setpoint.
A temperature setpoint of 22 °C and a relative humidity setpoint of 45 % with variations of ±2 °C
and ±15 %rh respectively are typical levels used for ofce spaces. Also, at high temperatures,
maximum limitation of absolute humidity should be provided to avoid “muggy” conditions. Typi-
cally, this limit value lies at about 10 g/kg (H
2
O).
Absolute humidity
rh = relative humidity
Temperature
Cooling and
humdifying
Heating and
humdifying
Humdifying and
reheating, if required
Humdifying only
Comfort range
35 %rh
24 °C
20 °C
65 %rh
Cooling only
Heating only
Energy savings
Besides the advantages in terms of indoor air quality, air conditioning offers also an energy sav-
ing potential. For example, while uncontrolled ventilation through open windows leads to large
amounts of heat being lost to the outside during the heating season or gained from the outside
during the cooling season, air conditioning systems provide possibilities to utilize the extra “free”
energy in heat recovery modules so that overall operating costs will be reduced.
The larger the area of the comfort range, the better the energy saving opportunities.
2.2 Purpose of ventilation
The purpose of ventilation is to introduce fresh air from outside into a building or room, in order
to control indoor air quality and thermal comfort.