2. SELECTING THE INSTALLATION SITE
2-1. Indoor Unit
AVOID:
areas where leakage of fl ammable gas may be expected.
places where large amounts of oil mist exist.
direct sunlight.
locations near heat sources which may affect the
performance of the unit.
locations where external air may enter the room directly. This
may cause “sweating” on the air discharge ports, causing
them to spray or drip.
locations where the remote controller will be splashed with
water or affected by dampness or humidity.
installing the remote controller behind curtains or furniture.
locations where high-frequency emissions are generated.
DO:
select an appropriate position from which every corner of the
room can be uniformly cooled.
select a location where the ceiling is strong enough to
support the weight of the unit.
select a location where tubing and drain pipe have the
shortest run to the outdoor unit.
allow room for operation and maintenance as well as
unrestricted air fl ow around the unit.
install the unit within the maximum elevation difference above
or below the outdoor unit and within a total tubing length (L)
from the outdoor unit as detailed in the installation manual
packed with the outdoor unit.
allow room for mounting the remote controller about 3 ft. off
the fl oor, in an area that is not in direct sunlight nor in the
ow of cool air from the indoor unit.
The elevation (Low Silhouette Ducted, Slim Low Static
Ducted) between the bottom unit and the fl oor surface should
be at least 8 feet.
If the elevation (Low Silhouette Ducted, Slim Low Static
Ducted) between them is less than 8 feet, install a fi lter
(optional/fi eld supply) or a protective device (fi eld supply) not
to touch the electrical parts or fan with hands.
The air intake and outtake openings should be provided with
the same location of a room.
NOTE
Air delivery will be degraded if the distance from the fl oor
to the ceiling is greater than 10 ft.
Slim Low Static Ducted Type
Low Silhouette Ducted (High Static Pressure) Type
4-Way Cassette (60 × 60) Type
3 ft.
3 ft.
3 ft.
3 ft.
3 ft.
10 in.
10 in.
10 in.
Fig. 2-1
Min.8 ft.
Shows Low Silhouette Ducted Type
and Slim Low Static Ducted Type
Fig. 2-2
Wall Mounted Type
Min.
6 in.
Min. 6 in.
Min.
6 in.
Front View
Fig. 2-3
Floor Standing, Concealed Floor Standing Type
Horizontal view Vertical view
min. 3.3 ft.
min. 3.3 ft.
min.
3-15/16"
min.
3-15/16"
Fig. 2-4
Ceiling Type
Front view
Side view
Min. 10 in. Min. 10 in.
Min. 2 ft.
Max. 10 in.
Obstacle
Air
discharge
Air intake
Ceiling
Wall
NOTE
The rear of the indoor unit can be installed fl ush against the wall.
Fig. 2-5
1-Way Cassette Type
Side view
Min. 3 ft.
Min. 2 in.
Min. 2 in.
Obstacle
Air
discharge
Air
intake
Ceiling
Wall
Wall
Fig. 2-6
VRF_Indoor_US.indb 9VRF_Indoor_US.indb 9 2011/09/30 12:22:552011/09/30 12:22:55