3. HOW TO INSTALL THE INDOOR UNIT
4-Way Cassette Type (U1 Type) ■
3-1. Preparation for Suspending
This unit uses a drain pump. Use a level gauge to check that the unit
is level.
3-2. Suspending the Indoor Unit
(1) Fix the suspension bolts securely in the ceiling using the method
shown in the diagrams (Figs. 3-1 and 3-2), by attaching them to
the ceiling support structure, or by any other method that ensures
that the unit will be securely and safely suspended.
(2) Follow Fig. 3-2 and Table 3-1 to make the holes in the ceiling.
Table 3-1
Unit: in. (mm)
Length
Type
ABCD
12, 18, 24, 36
31-1/32
(788)
28-15/32
(723)
34-27/32
(885)
34-27/32
(885)
(3) Determine the pitch of the suspension bolts using the supplied full-
scale installation diagram. The diagram and table (Fig. 3-3 and
Table 3-2) show the relationship between the positions of the
suspension fi tting, unit, and panel.
Table 3-2
Unit: in. (mm)
Length
Type
ABCDE
12, 18, 24
4-29/64
(113)
6-13/16
(173)
10-5/64
(256)
8-17/64
(210)
3-15/32
(88)
36
4-29/64
(113)
6-13/16
(173)
12-9/16
(319)
8-17/64
(210)
3-15/32
(88)
Note: For DC Fan Tap Change Procedure for
4-Way Cassette, see page 16.
Hole-in-anchor
Hole-in-plug
Concrete Inser t
Suspension bolt (M10 or 3/8")
(field supply)
Fig. 3-1
D (ceiling opening dimension)
C (ceiling opening dimension)
A (suspension bolt pitch)
B (suspension bolt pitch)
Fig. 3-2
3-3. Placing the Unit Inside the Ceiling
(1) When placing the unit inside the ceiling, determine the
pitch of the suspension bolts using the supplied full-
scale installation diagram. (Fig. 3-4)
Tubing and wiring must be laid inside the ceiling when
suspending the unit. If the ceiling is already
constructed, lay the tubing and wiring into position for
connection to the unit before placing the unit inside
the ceiling.
Drain outlet(other side)
(VP25)
Suspension lug
Refrigerant tubing joint(liquid side) Refrigerant tubing joint(gas side)
Power supply outlet
Inter-unit control wiring
D
E
A
B
C
1-3/8 (35)
Unit: in. (mm)
Fig. 3-3
Full-scale installation diagram
(printed on top of container box)
Supplied bolt
Over 19/32 (15)
15/32 – 43/64
(12 – 17)
Unit: in. (mm)
Fig. 3-4
VRF_Indoor_US.indb 10VRF_Indoor_US.indb 10 2011/09/30 12:22:562011/09/30 12:22:56