3-12. Checking the Drainage
After wiring and drain piping are completed, use the following
procedure to check that the water will drain smoothly. For this,
prepare a bucket and wiping cloth to catch and wipe up spilled
water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Slowly pour approx. 0.13 gal of water into the drain
pan to check drainage. (Fig. 3-37)
(3) Short the check pin (CHK) on the indoor control board
and operate the drain pump. Check the water fl ow
through the transparent drain pipe and see if there is
any leakage.
(4) When the check of drainage is complete, open the
check pin (CHK) and remount the tube cover.
CAUTION
Be careful since the fan will start
when you short the pin on the
indoor control board.
3-13. How to Install the Ceiling Panel
Checking the unit position
(1) Check that the ceiling hole is within this range:
23-5/8" × 23-5/8"
(2) Confi rm that the position of the indoor unit and the
ceiling as shown in the diagram. If the positions of the
ceiling surface and unit do not match, air leakage,
water leakage, fl ap operation failure, or other
problems may occur.
CAUTION
Never place the panel face-down. Either hang it vertically
or place it on top of a projecting object. Placing it face-
down will damage the surface.
Do not touch the fl ap or apply force to it. (This may
cause fl ap malfunction.)
3-13-1. Before Installing the Ceiling Panel
(1) Remove the air-intake grille and air fi lter from the
ceiling panel.
a) Slide the air-intake grille catches in the direction
shown by the arrows
1
to open the grille.
(Fig. 3-40)
b) With the air-intake grille opened, remove the grille
hinge from the ceiling panel by sliding it in the
direction shown by the arrow
2
. (Fig. 3-41)
(2) Removing the corner cover
a) Remove the screws on the corner and slide the
latches in the direction of the arrow
1
to
disconnect the hinges (3 locations). (Fig. 3-42)
Then, remove the air-intake grille in the direction of
the arrow
2
. (Fig. 3-43)
A
must be within the range of 33/64" to 45/64". (Fig. 3-38)
If not within this range, malfunction or other trouble may occur.
A
Main unit
Ceiling side
Ceiling opening
dimension
Screw
Latch
Water drain
Drain pan outlet
Water
(Approx. 0.13 gal)
Plastic container
for water intake
Over
3-15/16"
Fig. 3-37
Fig. 3-38
Flap
Fig. 3-39
2
1
1
Air-intake grille
Ceiling panel
Air-intake grille hinge
Fig. 3-40
Fig. 3-41
Corner cover
2
1
1
Push
Corner cover
Ceiling panel
Fig. 3-42
Fig. 3-43
VRF_Indoor_US.indb 19VRF_Indoor_US.indb 19 2011/09/30 12:22:592011/09/30 12:22:59