65
(1) When linking outdoor units in a network, disconnect the terminal extended from the short plug (CN003, 2P
Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the
outdoor units. (When shipping: In shorted condition.)
For a system without link (no connection wiring between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 4-1)
Outdoor unitOutdoor unit
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Outdoor unit
Prohibited
Prohibited
Fig. 4-1
(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes misaddress
setting. (Fig. 4-2)
Outdoor unit
NO
Indoor unit Indoor unit
Indoor unit Indoor unit
Branch point
Fig. 4-2
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
(Branches less than 3.3 ft. are not included in the total branch number.) (Fig. 4-3)
Outdoor unit Outdoor unit Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
more than 3.3 ft.
more than 3.3 ft.
16 or fewer
less than 3.3 ft.
Branch
point
Fig. 4-3
VRF_Indoor_US.indb 65VRF_Indoor_US.indb 65 2011/09/30 12:23:122011/09/30 12:23:12