16
3-6-5. Checking After Installation
Check that there are no gaps between the unit and the ceiling panel, or between the ceiling panel and the ceiling
●
surface. Gaps may cause water leakage and condensation.
Check that the wiring is securely connected.
●
If it is not securely connected, the auto fl ap will not operate. (“P09” is displayed on the remote controller.) In addition,
water leakage and condensation may occur.
3-6-6. When Removing the Ceiling Panel for Servicing
When removing the ceiling panel for servicing, remove the air-intake grille and air fi lter, disconnect the wiring connector
inside the electrical component box, and then remove the 4 mounting screws.
3-6-7. Adjusting the Auto Flap
The air-direction louver on the ceiling panel outlet can be adjusted as follows.
Adjust the louver to the desired angle using the remote controller. The louver also has an automatic air-sweeping
●
mechanism.
NOTE
Never attempt to move the louver by hand.
●
Proper air fl ow depends on the location of the air conditioner, the layout of the room and furniture, etc. If cooling or
●
heating seems inadequate, try changing the direction of the air fl ow.
3-7. Special Remarks
DC Fan Tap Change Procedure
Be sure to turn OFF the power (at mains) before beginning the work below.
(1) In the table below, check the fi eld-supply parts that will be used. (If this setting is not made, the airfl ow may
decrease and condensation may occur.)
Setting
(a)
Air shield material (for use with 3-direction discharge)*
Air shield material (for use when a discharge duct is connected)*
(b) Air shield material (for use with 2-direction discharge)*
* Use fi eld-supply air shield material.
Setting (a): Go to (2).
Setting (b): Go to (3).
(2) Setting (a)
Open the cover of the electrical component box. Short
the short-circuit pin TP3 (2P, yellow) on the indoor unit
control PCB. (Fig. 3-28)
(3) Setting (b)
Open the cover of the electrical component box. Short
the short-circuit pin TP6 (2P, white) on the indoor unit
control PCB. (Fig. 3-28)
Indoor unit control PCB
* PCB model No.: CR-SXRP56B-B
Fig. 3-28
VRF_Indoor_US.indb 16VRF_Indoor_US.indb 16 2011/09/30 12:22:582011/09/30 12:22:58