Design of 3WAY VRF SYSTEM
2 - 9
1
2
3
4
5
6
7
8
1. Model Selecting and Capacity Calculator
Gas tubing size (in.(mm))
1/2"
(12.7)
5/8"
(15.88)
3/4"
(19.05)
7/8"
(22.22)
1"
(25.4)
1-1/8"
(28.58)
1-3/8"
(38.1)
90° elbow
1 1.1 1.4 1.6 1.7 1.9 2.5
45° elbow
0.8 0.9 1
1.2
1.3 1.4 1.8
U-shape tube bent
(R2–23/64–3–15/16 in.)
3 3.4 4.1 4.7 5.1 5.6 7.4
T r ap bend
7.5 9.2 10.5 12.5 14.1 15.4 19.2
Y-branch distr ibution joint Equivalent length conversion not needed.
Ball v alve f or ser vice Equivalent length conversion not needed.
1-6. Straight Equivalent Length of Joints
Design the tubing system by referring to the following table for the straight equivalent length of joints.
Table 2-8 Straight Equivalent Length of Joints
Unit: ft.
TD831158-00_3WAY_VRF_SYS.indb 9TD831158-00_3WAY_VRF_SYS.indb 9 2012/01/23 17:30:122012/01/23 17:30:12