Indoor Unit Outdoor Unit
CS-S9NKUA
CS-S12NKUA
CU-S9NKUA
CU-S12NKUA
TABLE OF CONTENTS
1. Safety Precautions.............................................3
2. Specification .......................................................5
3. Location of Controls and Components ...........7
3.1 Indoor Unit....................................................7
3.2 Outdoor Unit.................................................7
3.3 Remote Control ............................................7
4. Dimensions.........................................................8
4.1 Indoor Unit....................................................8
4.2 Outdoor Unit.................................................9
5. Refrigeration Cycle Diagram...........................10
6. Block Diagram ..................................................11
7. Wiring Connection Diagram............................12
7.1 Indoor Unit..................................................12
7.2 Outdoor Unit...............................................13
8. Electronic Circuit Diagram ..............................14
8.1 Indoor Unit..................................................14
8.2 Outdoor Unit...............................................15
9. Printed Circuit Board .......................................16
9.1 Indoor Unit..................................................16
9.2 Outdoor Unit ...............................................18
10. Installation Instruction.....................................19
10.1 S9NKUA S12NKUA...................................19
11. Operation Control.............................................27
11.1 Basic Function............................................27
11.2 Indoor Fan Motor Operation.......................28
11.3 Outdoor Fan Motor Operation (For S9NK
and S12NK)................................................28
11.4 Airflow Direction .........................................28
11.5 Quiet Operation (Cooling Mode/Cooling Area
of Dry Mode)...............................................29
11.6 Powerful Mode Operation ..........................30
11.7 Timer Control..............................................30
11.8 Random Auto Restart Control ....................30
11.9 Indication Panel..........................................30
12. Protection Control............................................31
PRECAUTION OF LOW TEMPERATURE
In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit.
WARNING
This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to
service or repair the products dealt with in this service information by anyone else could result in serious injury or death.
Vista de pagina 0
1 2 3 4 5 6 ... 73 74

Indice de contenidos

Pagina 1

© Panasonic HA Air-Conditioning (M) Sdn. Bhd. 2011. Unauthorized copying and distribution is a violation of law. Order No: PHAAM1111085C1 Indoor Un

Pagina 2

10 5. Refrigeration Cycle Diagram INDOOR OUTDOORINTAKETEMP.SENSORPIPETEMP.SENSORLIQUIDSIDE2-WAYVALVE4-WAYVALVEGASSIDECOOLINGHEAT EXCHANGER(EVAPORATOR

Pagina 4 - CAUTION

12 7. Wiring Connection Diagram 7.1 Indoor Unit

Pagina 5 - 2. Specification

13 7.2 Outdoor Unit

Pagina 6

14 8. Electronic Circuit Diagram 8.1 Indoor Unit

Pagina 8 - 4. Dimensions

16 9. Printed Circuit Board 9.1 Indoor Unit 9.1.1 Main Printed Circuit Board

Pagina 9 - 4.2 Outdoor Unit

17 9.1.2 Power Printed Circuit Board 9.1.3 Indicator Printed Circuit Board

Pagina 10 - INDOOR OUTDOOR

18 9.2 Outdoor Unit 9.2.1 Main Printed Circuit Board

Pagina 11 - 6. Block Diagram

19 10. Installation Instruction 10.1 S9NKUA S12NKUA 10.1.1 Select the Best Location 10.1.1.1 Indoor Unit • Do not install the unit in excessive oi

Pagina 12 - 7. Wiring Connection Diagram

2 12.1 Restart Control (Time Delay Safety Control).. ...31 12.2 30 Seconds Forced O

Pagina 13 - 7.2 Outdoor Unit

20 10.1.3 Indoor Unit 10.1.3.1 How to Fix Installation Plate The mounting wall shall be strong and solid enough to prevent if from the vibration.

Pagina 14 - 8.1 Indoor Unit

21 10.1.3.3 Indoor Unit Installation 10.1.3.4 For the right rear piping 10.1.3.5 For the right bottom piping 10.1.3.6 For the embedded piping

Pagina 15 - 8.2 Outdoor Unit

22 10.1.3.7 Connect the Cable to the Indoor Unit 1. The inside and outside connection cable can be connected without removing the front grille. 2

Pagina 16 - 9. Printed Circuit Board

23 10.1.3.8 Wire Stripping and connecting requirement 10.1.3.9 Cutting and flaring the piping 1 Please cut using pipe cutter and then remove the

Pagina 17

24 10.1.4 Outdoor Unit 10.1.4.1 Install the Outdoor Unit • After selecting the best location, start installation to Indoor/Outdoor Unit Installation

Pagina 18 - 9.2 Outdoor Unit

25 10.1.4.3 Evacuation of the equipment WHEN INSTALLATION AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the fol

Pagina 19 - 10. Installation Instruction

26 9. Secure the wire onto the control board with the holder (clamper). 10. After completing wiring connections, reattach the control board cover (

Pagina 20 - Install a Sleeve of Piping

27 11. Operation Control 11.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operation mode as

Pagina 21

28 11.2 Indoor Fan Motor Operation 11.2.1 Basic Rotation Speed • Manual Fan Speed o Fan motor’s number of rotation is determined according to remot

Pagina 22

29 11.4.1 Vertical Airflow Vane Angle (°) Operation Mode Airflow Direction 1 2 3 4 5 Auto 20 ~ 45 Cooling Manual 20 26 32 37 45 Auto 20 ~ 45 Soft

Pagina 23

3 1. Safety Precautions • Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. • Electrical work must be installed or ser

Pagina 24

30 11.6 Powerful Mode Operation • When the powerful mode is selected, the internal setting temperature will shift lower up to 35.6°F (for Cooling/S

Pagina 25 - with a torque wrench

31 12. Protection Control 12.1 Restart Control (Time Delay Safety Control) • The compressor will not turn on within 3 minutes from the moment oper

Pagina 26 - 10.1.4.5 Piping Insulation

32 12.5 Low Pressure Protection Control (Gas Leakage Detection) • Control start conditions o For 5 minutes, the compressor continously operates

Pagina 27 - 11. Operation Control

33 12.10 Freeze Prevention Control • When indoor heat exchanger temperature is lower than 32°F continuously for 6 minutes, compressor will stops op

Pagina 28 - 11.4 Airflow Direction

34 13. Servicing Mode 13.1 Auto Off/On Button Auto OFF/ON Button Pressed Auto OFF/ON Button Pressed 5 sec Auto Operation Test Run Operation (

Pagina 29 - 11.4.2.1 S9NK, S12NK

35 13.2 Remote Control Button 13.2.1 SET Button • To check remote control transmission code and store the transmission code to EEPROM o Press “Set”

Pagina 30 - 11.9 Indication Panel

36 14. Troubleshooting Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical pr

Pagina 31 - 12. Protection Control

37 14.1.1 Relationship between the condition of the air conditioner and pressure and electric current Cooling Mode Condition of the air conditioner

Pagina 32

38 14.2 Breakdown Self Diagnosis Function 14.2.1 Self Diagnosis Function (Three Digits Alphanumeric Code) • Once error occurred during operation, t

Pagina 33

39 14.3 Error Code Table Diagnosis display Abnormality / Protection control Abnormality JudgmentEmergency Operation Primary location to verify H00

Pagina 34 - 13. Servicing Mode

4 WARNING 19. During installation, install the refrigerant piping properly before run the compressor. (Operation of compressor without fixing refrig

Pagina 35 - 13.2 Remote Control Button

40 14.4 Troubleshooting Flowchart 14.4.1 H11 (Indoor/Outdoor Abnormal Communication) Malfunction Decision Conditions • During startup and operation

Pagina 36 - 14. Troubleshooting Guide

41 14.4.2 H12 (Indoor/Outdoor Capacity Rank Mismatched) Malfunction Decision Conditions • During startup, error code appears when different types of

Pagina 37

42 14.4.3 H14 (Indoor Intake Air Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heati

Pagina 38 - 14.2.2 To Make a Diagnosis

43 14.4.4 H15 (Compressor Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heating, the

Pagina 39 - 14.3 Error Code Table

44 14.4.5 H16 (Outdoor Current Transformer Open Circuit) Malfunction Decision Conditions • A current transformer (CT) is detected by checking the co

Pagina 40

45 14.4.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions • The rotation speed detected by the Hall IC during fan

Pagina 41

46 14.4.7 H23 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heating, th

Pagina 42

47 14.4.8 H27 (Outdoor Air Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heating, th

Pagina 43

48 14.4.9 H28 (Outdoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heating,

Pagina 44

49 14.4.10 H30 (Compressor Discharge Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and h

Pagina 45

5 2. Specification Indoor CS-S9NKUA CS-S12NKUA Model Outdoor CU-S9NKUA CU-S12NKUA Performance Test Condition ARI ARI Phase, Hz Single, 60 Single

Pagina 46

50 14.4.11 H33 (Unspecified Voltage between Indoor and Outdoor) Malfunction Decision Conditions • The supply power is detected for its requirement

Pagina 47

51 14.4.12 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions • The rotation speed detected by the Hall IC during f

Pagina 48

52 14.4.13 H98 (Indoor High Pressure Protection) Error Code will not display (no Timer LED blinking) but store in EEPROM Malfunction Decision Condit

Pagina 49

53 14.4.14 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) Malfunction Decision Conditions • Freeze prevention control takes place

Pagina 50

54 14.4.15 F11 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions • When cooling operation, when indoor pipe temperature

Pagina 51

55 14.4.16 F90 (Power Factor Correction Protection) Malfunction Decision Conditions • During startup and operation of cooling and heating, when Po

Pagina 52

56 14.4.17 F91 (Refrigeration Cycle Abnormality) Malfunction Decision Conditions • During cooling, compressor frequency = Fcmax. • During cooling

Pagina 53

57 14.4.18 F93 (Compressor Rotation Failure) Malfunction Decision Conditions A compressor rotation failure is detected by checking the compressor r

Pagina 54

58 14.4.19 F95 (Cooling High Pressure Abnormality) Malfunction Decision Conditions During operation of cooling, when outdoor unit heat exchanger hi

Pagina 55

59 14.4.20 F96 (IPM Overheating) Malfunction Decision Conditions During operating of cooling and heating, when IPM temperature data (212°F) is dete

Pagina 56

6 Control Device Capillary Tube Capillary Tube Refrigerant Oil cm3 FV50S (320) FV50S (320) Refrigeration Cycle Refrigerant Type g (oz) R410A,

Pagina 57

60 14.4.21 F97 (Compressor Overheating) Malfunction Decision Conditions During operation of cooling and heating, when compressor tank temperature d

Pagina 58

61 14.4.22 F98 (Input Over Current Detection) Malfunction Decision Conditions During cooling and heating operation, when an input over-current (16.

Pagina 59

62 14.4.23 F99 (Output Over Current Detection) Malfunction Decision Conditions During operation of cooling and heating, when an output over-current

Pagina 60

63 WARNING 15. Disassembly and Assembly Instructions High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capa

Pagina 61

64 15.1.1.2 To remove discharge grille

Pagina 62 - Abnormal resistance 0 or ∞

65 15.1.1.3 To remove control board 15.1.1.4 To remove cross flow fan and indoor fan motor

Pagina 64

67 16. Technical Data 16.1 Operation Characteristics 16.1.1 CS-S9NKUA CU-S9NKUA • Cooling Characteristic o Room temperature: 81°F (DBT), 66°F (WBT)

Pagina 65

68 • Piping Length Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature: 95°F

Pagina 66

69 16.1.2 CS-S12NKUA CU-S12NKUA • Cooling Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Piping

Pagina 67 - 16. Technical Data

7 3. Location of Controls and Components 3.1 Indoor Unit 3.2 Outdoor Unit 3.3 Remote Control

Pagina 68

70 • Piping Length Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature: 95°F

Pagina 69 - 16.1.2 CS-S12NKUA CU-S12NKUA

71 17. Exploded View and Replacement Parts List 17.1 Indoor Unit 17.1.1 CS-S9NKUA CS-S12NKUA Note The above exploded view is for the purpose of p

Pagina 70

72 REF. NO. PART NAME & DESCRIPTION QTY. CS-S9NKUA CS-S12NKUA REMARK 1 CHASSIS COMPLETE 1 CWD50C1633 ← 2 FAN MOTOR 1 L6CBYYYL0055 ← O

Pagina 71 - 17.1 Indoor Unit

73 17.2 Outdoor Unit 17.2.1 CU-S9NKUA CU-S12NKUA Note The above exploded view is for the purpose of parts disassembly and replacement. The non-nu

Pagina 72

74 REF. NO. PART NAME & DESCRIPTION QTY. CU-S9NKUA CU-S12NKUA REMARK 1 CHASSIS ASSY 1 CWD50K2206A ← 2 FAN MOTOR BRACKET 1 CWD541089

Pagina 73 - 17.2 Outdoor Unit

8 4. Dimensions 4.1 Indoor Unit

Pagina 74

9 4.2 Outdoor Unit