Design of 3WAY VRF SYSTEM
2 - 7
1
2
3
4
5
6
7
8
1. Model Selecting and Capacity Calculator
Liquid tubing size Amount of refrigerant
(in. (mm)) charge (oz/ft.)
ø1/4" (ø6.35) 0.279
ø3/8" (ø9.52) 0.602
ø1/2" (ø12.7) 1.38
ø5/8" (ø15.88) 1.99
ø3/4" (ø19.05) 2.78
ø7/8" (ø22.22) 3.93
Table 2-5 Amount of Refrigerant Charge
Material O Material 1/2H • H
ø1/4" (ø6.35) t1/32 (t0.8)
ø3/8" (ø9.52) t1/32 (t0.8) ø1-1/8" (ø28.58) t5/128 (t1.0)
ø1/2" (ø12.7) t1/32 (t0.8) ø1-1/4" (ø31.75) t3/64 (t1.1)
ø5/8" (ø15.88) t5/128 (t1.0) ø1-1/2" (ø38.10)
ø3/4" (ø19.05)
ø1-5/8" (ø41.28)
ø7/8" (ø22.22) t5/128 (t1.0)
*
Unit: in. (mm)
e
Discharge tubing
Liquid tubing
Suction tubing
Indoor unit type
7
12 15 18 19 24 36 48 54
ø5/8" (ø15.88)
ø1/2" (ø12.7)
ø3/8" (ø9.52)
Gas tubing
Liquid tubing
ø1/2" (ø12.7)
ø1/4" (ø6.35)
ø5/8" (ø15.88)
ø3/8" (ø9.52)
Table 2-6 Indoor Unit Tubing Connection Size ( 1– 40 )
Table 2-7 Refrigerant tubing (Existing tubing can be used.)
Distribution
joint-solenoid
valve kit tubing
Solenoid valv
kit-Indoor
unit tubing
connection
over t5/128 (t1.0)
over t3/64 (t1.15)
over t3/64 (t1.20)
Tubing size (in. (mm))
When bending the tubes, use a bending
radius that is at least 4 times the outer
diameter of the tubes.
In addition, take sufficient care to avoid
crushing or damaging the tubes when
bending them.
*1: For the solenoid valve kits, use type 160 with parallel specifications. Branch the tubing before and after the solenoid valve kits.
9
TD831158-00_3WAY_VRF_SYS.indb 7TD831158-00_3WAY_VRF_SYS.indb 7 2012/01/23 17:30:112012/01/23 17:30:11