Installation and operation manual
4
S-20~125FM3HPQ
Urban Multi air conditioner
4PW15114-1A
■
Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.
■
Refer to Table 1 for the dimensions of flare nut spaces and the
appropriate tightening torque. (Overtightening may damage the
flare and cause leaks.)
Table 1
■
When connecting the flare nut, coat the flare both inside and
outside with ether oil or ester oil and initially tighten by hand 3 or
4 turns before tightening firmly.
Coat here with ether oil or ester oil
■
Check the pipe connector for gas leaks, then insulate it.
D
RAIN
PIPING
WORK
Rig the drain piping as shown in the figure and take measures
against condensation. Improperly rigged piping could lead to leaks
and eventually wet furniture and belongings.
1
Install the drain pipes.
-Keep piping as short as possible and slope it downwards so
that air may not remain trapped inside the pipe.
-Keep pipe size equal to or greater than that of the connecting
pipe (vinyl pipe of 25 mm nominal diameter and 32 mm outer
diameter).
- Use the supplied drain hose and metal clamp. Tighten the
clamp firmly.
■
Insulate the drain hose inside the building.
■
If the drain hose cannot be sufficiently set on a slope, fit the
hose with drain raising piping (field supply).
HOW TO PERFORM PIPING (See figure 8)
■
Connect the drain hose to the drain raising pipes, and insulate
them.
■
Connect the drain hose to the drain pipe on the indoor unit, and
tighten it with the metal clamp.
-To ensure a downward slope of 1:100, install hanging bars
every 1 to 1.5 m.
- If unifying multiple drain pipes, install the pipes as shown in
figure 9.
2
After piping work is finished, check if drainage flows smoothly.
- Open the water inlet lid, add approximately 1 l of water
gradually and check the drainage flow. (See figure 10)
1
Torque wrench
2 Spanner
3 Piping union
4 Flare nut
Pipe
gauge
Tightening torque
Flare dimension
A (mm)
Flare shape
Ø6.4 14.2~17.2 N•m
(144~176 kgf•cm)
8.7~9.1
Ø9.5 32.7~39.9 N•m
(333~407 kgf•cm)
12.8~13.2
Ø12.7 49.5~60.3 N•m
(504~616 kgf•cm)
16.2~16.6
Ø15.9 61.8~75.4 N•m
(630~770 kgf•cm)
19.3~19.7
1 Liquid pipe
2 Gas pipe
3 Insulation for fitting of liquid line
(supplied with the unit)
4 Insulation for fitting of gas line
(supplied with the unit)
5 Clamps (use 2 clamps per
insulation)
2
3
1
4
R=0.4~0.8
45°
±2
90°
±2
A
5
3
1
24
1 Hanging bar
1 Metal clamp
2 Drain hose
3 White tape (field
supply)
1 Ceiling slab
2 Hanging bar
3 Adjustable range
4 Drain hose (supplied with the unit)
5 Metal clamp (supplied with the unit)
6 Drain raising pipe (field supply)
Installation A
Rear suction installation 275
When canvas duct is installed 350-530
When air inlet panel is directly installed 275
1 Multiple drain piping
1 Water inlet
2 Portable pump
3 Water inlet lid
4 Bucket (adding water from water inlet)
5 Drain outlet for maintenance (with rubber drain plug)
6 Refrigerant pipes
1-1.
21
3