10.3.4 Connect the cable to the Outdoor Unit
1 Remove the control board cover from the unit by loosening the screw.
2 Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4x
1.5mm
2
flexible cords, type designation 245 IEC 57 or heavier cord.
3 Secure the cable onto the control board with the holder (clamper).
4 Attach the control board cover back to the original position with the screw.
5 For wiring stripping and connection requirement, refer to instruction 10.2.4 of indoor unit.
10.3.5 Pipe Insulation
1 Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please warp the insulated piping end to prevent water from going inside the piping.
2 If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E-FOAM with thickness 6mm or above.