31
System Configuration File
If there are more than one serial ports on the WV-ASC970 Server, you need to enter the correct port number in the
[REDUNDANT] section of the sys.ini file.
For Manual Switchover Operation
1. Connect the Ethernet cable between the SYSTEM CONTROLLER ports of both WV-ASC970 Servers.
(SERIAL ports are not used for MANUAL operation.)
2. Turnonthe"Redundant"checkboxonAdminConsole'sDomain>CPUUnits>Unittabandinputthebackup
WV-ASC970Server'sIPAddressto"BackupIPA"field.
3. Select the "Man (Redundant Manual Switchover)" radio button, and then click the "Mode" button.
4. Put the global database to both WV-ASC970 Servers and reboot both.
Note:
• IftheglobaldatabaseisputtoonlyoneWV-ASC970Server,theredundantfunctiondoesnotworkproperly.
5. By using the Admin Console, click the "Get CPU Status" button on Unit tab.
6. After Admin Console get the current WV-ASC970 status, click the "Switch Active CPU" button. At this point, the
dialog box will be displayed. Select "Switchover", then click "OK" button.
7. The Active WV-ASC970 Server reboots automatically, and moves to Standby state. Another WV-ASC970 Server
moves to Active state.
For Automatic Switchover Operation
1. Connect the 9-pin D-sub cross cable (locally procured) between the SERIAL ports of both WV-ASC970 Servers,
and connect the Ethernet cable between the SYSTEM CONTROLLER ports of the Servers.
2. Turnonthe"Redundant"checkboxonAdminConsole's"Domain">"CPUUnits">"Unit"tabandinputthe
backupWV-ASC970Server'sIPAddressto"BackupIPA"field.
3. Select the "Auto (Redundant Auto Switchover)" radio button and then, click the "Mode" button.
4. Put the global database to both WV-ASC970 Servers and turn off both servers.
Note:
• IftheglobaldatabaseisputtoonlyoneWV-ASC970Server,theredundantfunctiondoesnotworkproperly.
• Whenactivatingautomaticswitchoveroperation,usershouldnotregisteracontrollertotheSERIALportinthe
CONTROLLERS menu of admin console.
5. Turn on Main WV-ASC970 Server first. After it ups, turn on Backup WV-ASC970 Server.
6. When a fatal application software error happens in the Active WV-ASC970 Server, the Standby one will switcho-
ver automatically.
When a fatal OS system error happens in the Active WV-ASC970 Server, the Standby one may automatically
switch-over but the Active WV-ASC970 Server may need to reset manually.
Note:
• IftheStandbyWV-ASC970Serveralsohasfatalerror,theswitchoverisnotperformed.
• Whenthe9-pinD-subcrosscableisdisconnected,theStandbyWV-ASC970ServerwillbecomeActive,and
the Active WV-ASC970 Server will reboot.
WV-ASC970 Redundant Monitor Software
Administrator or Operator can perform the switchover operation by using the "Redundant Monitor" software includ-
ed in WV-ASC970 CD-ROM. Refer to the "Server Installer/Utility Operation Guide", "Redundant Monitor" section.