Panasonic CU-2E18NBU Manual de servicio

Busca en linea o descarga Manual de servicio para Acondicionadores de aire del sistema de división Panasonic CU-2E18NBU. Panasonic CU-2E18NBU Service Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 57
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
© Panasonic HA Air-Conditioning (M) Sdn. Bhd. 2011.
Unauthorized copying and distribution is a violation of law.
Order No: PHAAM1111120A1
Outdoor Unit
CU-2E18NBU
Please file and use this manual together with the service manual for Model No. CS-E9NKUAW CS-E12NKUAW, Order No.
PHAAM1111087C1.
TABLE OF CONTENTS
1. Safety Precautions.............................................3
2. Specifications.....................................................5
2.1 CU-2E18NBU...............................................5
3. Dimensions.........................................................8
4. Refrigeration Cycle Diagram.............................9
5. Block Diagram ..................................................10
6. Wiring Connection Diagram............................11
7. Electronic Circuit Diagram ..............................12
8. Printed Circuit Board .......................................13
8.1 Main Printed Circuit Board .........................13
8.2 Noise Filter Printed Circuit Board...............14
8.3 Display Printed Circuit Board .....................14
9. Installation Information ...................................15
9.1 Check Points ..............................................15
10. Installation Instruction.....................................16
10.1 Select The Best Location ...........................16
10.2 Install The Outdoor Unit .............................17
10.3 Connect the Piping.....................................17
10.4 Evacuation of the Equipment .....................18
10.5 Connect The Cable To The Outdoor
Unit .............................................................19
10.6 Heat Insulation ...........................................19
11. Operation Control.............................................20
11.1 Cooling Operation ......................................20
11.2 Heating Operation ......................................21
12. Simultaneous Operation Control....................22
13. Protection Control............................................23
13.1 Freeze Prevention control (Cool) ...............23
13.2 Dew Prevention control (Cool) ...................23
13.3 Electronic Parts Temperature Rise
Protection 1 (Cool) .....................................23
PRECAUTION OF LOW TEMPERATURE
In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit.
WARNING
This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to
service or repair the product or products dealt with in this service information by anyone else could result in serious injury or death.
Vista de pagina 0
1 2 3 4 5 6 ... 56 57

Indice de contenidos

Pagina 1 - TABLE OF CONTENTS

© Panasonic HA Air-Conditioning (M) Sdn. Bhd. 2011. Unauthorized copying and distribution is a violation of law. Order No: PHAAM1111120A1 Outdoor U

Pagina 2

10 5. Block Diagram

Pagina 3 - 1. Safety Precautions

11 6. Wiring Connection Diagram

Pagina 4

12 7. Electronic Circuit Diagram

Pagina 5 - 2. Specifications

13 8. Printed Circuit Board 8.1 Main Printed Circuit Board

Pagina 6 - •” : Available

14 8.2 Noise Filter Printed Circuit Board 8.3 Display Printed Circuit Board

Pagina 7

15 9. Installation Information 9.1 Check Points QUICK GUIDE PIPING AND ELECTRICAL SPECIFICATION Piping size Indoor (ID) & Outdoor (OD) units: Po

Pagina 8 - 3. Dimensions

16 10. Installation Instruction10.1 Select The Best Location 10.1.1 Outdoor Unit  If an awning is built over the unit to prevent direct sunlight or

Pagina 9

17 Outdoor Unit Installation Guidelines  Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the insta

Pagina 10 - 5. Block Diagram

18 CUTTING AND FLARING THE PIPING 1 Please cut using pipe cutter and then remove the burrs. 2 Remove the burrs by using reamer. If burrs is not remo

Pagina 11 - 6. Wiring Connection Diagram

19 10.5 Connect The Cable To The Outdoor Unit 1 Remove Control Board Cover (Metal) by loosening 2 screws. 2 Remove Valve Cover (Metal) by loosening

Pagina 12

2 13.4 Electronic Parts Temperature Rise Protection 2 (Cool)...23 13.5 Cooling overload control (Cool)...

Pagina 13 - 8. Printed Circuit Board

20 11. Operation Control 11.1 Cooling Operation 11.1.1 Outdoor fan control  When cooling operation is enabled, based on outdoor ambient temperature

Pagina 14

21 11.2 Heating Operation 11.2.1 Outdoor fan control  When heating operation is enabled, based on outdoor ambient temperature, fan motor control wi

Pagina 15 - 9. Installation Information

22 12. Simultaneous Operation Control 1 Operation modes which can be selected using the remote control unit: Automatic, Cooling, Soft Dry, Heating,

Pagina 16 - 10. Installation Instruction

23 13. Protection Control 13.1 Freeze Prevention control (Cool)  When received freeze prevention signal from indoor unit, the compressor frequency

Pagina 17 - 10.3 Connect the Piping

24 13.5 Cooling overload control (Cool)  This control detect outdoor pipe temperature and perform the compressor frequency restriction during cooli

Pagina 18

25 13.8 Deice Control  When outdoor pipe temperature and outdoor air temperature is low, deice operation starts where indoor fan motor and outdoor f

Pagina 19 - 10.6 Heat Insulation

26 13.13 Compressor Protection Control (Gas leak detection control 1)  Control start conditions o For 5 minutes, the compressor continuously oper

Pagina 20 - 11. Operation Control

27 14. Servicing Mode 14.1 CU-2E18NBU 14.1.1 Pump down operation (SW1)  Operate the pump down process according to the following procedure o Con

Pagina 21 - 11.2 Heating Operation

28 14.1.3 Wiring Error check  The unit capable to correct the wiring error automatically by following procedures. o Confirm the valve on the liqui

Pagina 22

29 15. Troubleshooting Guide 15.1 Self Diagnosis Function  The display screen of wireless remote control unit and the self-diagnosis LEDs (green) o

Pagina 23 - 13. Protection Control

3 CAUTION WARNING WARNING 1. Safety Precautions  Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing.  Electrical work

Pagina 26

32 WARNING 16. Disassembly and Assembly Instructions High Voltage are generated in the electrical parts area by the capacitor. Ensure that the cap

Pagina 27 - 14. Servicing Mode

33 16.1.3 Removing the Control P.C. Board 6 Remove the drip proof cover. 7 Disconnect the connectors (lead wires of the compressor, sensor

Pagina 28 - 14.1.4 Power Save Mode

34 3 Disconnect the fan motor connector from the control P.C. Board. 4 Loosen the 4 fan motor mounting screws then remove the fan motor.

Pagina 29 - 15. Troubleshooting Guide

35 17. Technical Data 17.1 Operation Characteristics 17.1.1 One Indoor Unit Operation  Cooling Characteristic [Condition] Room temperature: 81°F

Pagina 30

36  Cooling Characteristic [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan speed Piping Length: 24.6ft Comp

Pagina 31

37  Piping Length Characteristic Cooling [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan speed Outdoor tempe

Pagina 32

38  Piping Length Characteristic Cooling [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan speed Outdoor tempe

Pagina 33

39  Heating Characteristic [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Piping Length: 24.6ft Compressor Freq:

Pagina 34

4 CAUTION 18. For R410A models, when connecting the piping, do not use any existing (R22) pipes and flare nuts. Using such same may cause abnorm

Pagina 35 - 17. Technical Data

40  Heating Characteristic [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Piping Length: 24.6ft Compressor Freq:

Pagina 36 -  Cooling Characteristic

41  Piping Length Characteristic Heating [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Outdoor temperature: 47°F

Pagina 37

42  Piping Length Characteristic Heating [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Outdoor temperature: 47°F

Pagina 38

43 17.1.2 Two Indoor Unit Operation  Cooling Characteristic [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan s

Pagina 39 -  Heating Characteristic

44  Cooling Characteristic [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan speed Piping Length: 24.6ft Comp

Pagina 40

45  Cooling Characteristic [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan speed Piping Length: 24.6ft Comp

Pagina 41

46  Piping Length Characteristic Cooling [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan speed Outdoor tempe

Pagina 42

47  Piping Length Characteristic Cooling [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan speed Outdoor tempe

Pagina 43

48  Piping Length Characteristic Cooling [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan speed Outdoor tempe

Pagina 44

49  Heating Characteristic [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Piping Length: 24.6ft Compressor Freq:

Pagina 45

5 2. Specifications 2.1 CU-2E18NBU Item Unit OUTDOOR UNIT Indoor Unit Combination 3.2kW + 3.2kW Power Source 1 Phase, 208 – 230V, 60Hz (Power

Pagina 46

50  Heating Characteristic [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Piping Length: 24.6ft Compressor Freq:

Pagina 47

51  Heating Characteristic [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Piping Length: 24.6ft Compressor Freq:

Pagina 48

52  Piping Length Characteristic Heating [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Outdoor temperature: 47°F

Pagina 49

53  Piping Length Characteristic Heating [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Outdoor temperature: 47°F

Pagina 50

54  Piping Length Characteristic Heating [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Outdoor temperature: 47°F

Pagina 51

55 18. Exploded View and Replacement Parts List Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numb

Pagina 52

56 REF. NO. DESCRIPTION & NAME Q’TY CU-2E18NBU REMARK 1 BASE PAN ASS'Y 1 CWD52K1239A 2 SOUND-PROOF BOARD 1 CWH151230 3 FAN MOTO

Pagina 53

57 74 ACCESSORY CO. (DRAIN ELBOW) 1 CWG87C900 76 NUT - TERMINAL COVER 2 CWH7080300J 77 TERMINAL COVER 1 CWH171035 78 TUBE ASS'Y (L

Pagina 54

6 Item Unit OUTDOOR UNIT Air Volume High m3/min (ft3/min) 37.2 (1313) Refrigerant Control Device Expansion Valve Refrigerant Oil FV50S Ref

Pagina 55

7 Indoor unit combination Cooling Capacity (kW) Input Power (W) Outdoor Unit Operation Class (kW) Operation Mode Rating Min ~ Max Rating Min ~ Ma

Pagina 56

8 3. Dimensions

Pagina 57

9 4. Refrigeration Cycle Diagram

Comentarios a estos manuales