Split System Submittal Data
System: 26PEU1U6 Indoor: S-26PU1U6 Outdoor: U-26PE1U6
Single Split System - Ceiling Recessed Heat Pumps
Approval:
Date:
Construction:
Unit#:
Drawing#:
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
General Data
Power (V/P/Hz) 230/208/1/60
Circuit Ampacity (A) 15-30 Indoor-Outdoor
Fuse Size, Max.(A) 15-30 Indoor-Outdoor
Compressor DC Rotary Inverter
No. Used 1
R.L. Amps - L.R. (A) 12.9 - 17.5
Outdoor Unit
Fan type Propeller
Dia & Length (in.) - No. used 18-7/64-1
Type Drive - No. Speeds DC Motor
No. Poles (RPM) 8 - 800
No. Motors (W) 1 - 90
CFM (High) 1765
F.L. Amps (A) 13.8
Coil Type Aluminum Fin & Copper Pipe
Fin Type - Pipe Type Slit Plate - Inner Rifled
Rows - F.P.I. 1 - 15.9
Face Area (sq.ft.) 7.26
Tube Size (in) 3/8"
Indoor Unit
Fan type Turbo
Dia & Length (in.) - No. used 17-7/16-1
No. Speeds 3 & Auto
No. Poles (RPM, High) 6 - 464
No. Motors (W) 1 - 40
CFM (HI/Med/Lo) 710/530/450
Indoor Sound Rating (Hi) (dB-A) 38
F.L. Amps (A) 0.7
Coil Type
Aluminum Plate Fin & Copper Tube
Fin Type - Pipe Type Slit Plate - Inner Rifled
Rows - F.P.I. 2 - 14.9
Face Area (sq.ft.) 3.69
Tube Size (in) 9/32"
Drain Connection Size (in.) 1-17/64"
Refrigerant R410A
Lbs. - R410a 4.19
Control Electric Expansion Valve
Connection Flare
Line Length, Max (ft.) 165
Line Difference, Max (ft.) 50 (outdoor lower),
100 (outdoor higher)
Line Size (in. O.D. Discharge) 3/8"
Line Size (in. O.D. Suction) 5/8"
Dimensions (HxWxD)
Indoor Unit (Crated) (in.) 11-9/64 x 32-7/8 x 33-9/32
Indoor Unit (Uncrated) (in.) 13-5/16 x 33-55/64 x 33-55/64
Outdoor Unit (Crated) (in.) 34-31/32 x 39-31/32 x 16-3/32
Outdoor Unit (Uncrated) (in.) 30-23/32 x 37 x 13-3/8
Weight (lbs.)
(Indoor) Net 49
(Indoor) Shipping 57
(Outdoor) Net 128
(Outdoor) Shipping 148
(Indoor) Shipping Volume (cu.ft.) 7.1
(Outdoor) Shipping Volume (cu.ft.) 13